About the article
G.A. Tumanov, A.V. Starovoitov, E.I. Laguseva, K.V. Chalov, N.Yu. Starovoitova, V.Yu. Doluda
. In the article practical and theoretical issues of determining the settling time of foams for fire extinguishing solutions are considered. Aqueous foam-forming solutions containing 1–2 wt.% sodium decylsulfate, 0,5–2 wt.% sodium sulfoethoxylate, 0,1–0,5 wt.% butanol, 0,1–0,5 wt.% lignosulfonate technical were investigated. The foam settling time was determined by the settling time of 50 % of the foam column. For this purpose 20 ml of the prepared foam-forming solution was poured into a measuring cylinder, after which air was blown through it for 3 min at a flow rate of 50, 100, 150, 200 ml/min. The dependence of the settling time of half of the foam column on the complex , which is described by the steppe function τ½ = 2,355 6(µro /(gρ))–0,211 with an approximation reliability of 95 %, was found. It is concluded that the provision of acceptable foam stability is possible for values of the complex not more than 10–9 m2 s.
stability, foam, foam settling time, stability, foam settling velocity.