About the article
I.P. Popov
The results of the evaluation of the influence of the transformer cascade on the reactive power in the network under symmetrical load are presented. A number of important conclusions are presented: in the considered scheme, with a symmetrical load, reactive power self-compensates; if the transformers are identical, then the reactive power flow from the load is divided between them into equal parts; the reactive power flow in the external section is three times less than in the internal one. It is indicated that in a real network, due to the above circumstances, the reactive power flow decreases significantly with an increase in the number of transformer substations as it moves away from the load.
oscillator, energy, oscillations, reactive power, phase, cascade, transformer, network, symmetrical load.